M-CenterApplication

RS485 (Modbus RTU) to MQTT: gateway with the EMU M-Center

The EMU M-Center reads devices with RS485 (Modbus RTU) and publishes their values via MQTT to your broker. No PC in between, in parallel with M-Bus meters and other interfaces.

Key facts

  • Two RS-485 lines, up to 64 Modbus RTU devices depending on the licence (32 or 64).
  • Per device: serial number, slave address, baud rate, parity, stop bit, byte and word order.
  • Own topic per device and register, by register number or OBIS code.
  • MQTT 3.1, 3.1.1 and 5, TLS, QoS 0, 1 or 2.
  • Required: M-Center base unit plus licence 210.200.00 or 210.200.01 and licence 210.300.03.
2885.6Professional II RS485Slave 1 · SN 22231100
1412.3Professional II RS485Slave 2 · SN 22231101
3207.9Professional II RS485Slave 3 · SN 22231102
EMU M-CenterModbus RTU master · MQTT client · 10:2C:EF:02:6C:B9
EMU M-CenterModbus RTU master
Register 6000 · active energy import
Slave 1SN 22231100–
Slave 2SN 22231101–
Slave 3SN 22231102–
MQTT brokerlocal or in the cloud
Topics
haus-a/emu/mcenter/10:2C:EF:02:6C:B9/meterreading/
Subscribers
Home AssistantNode-REDGrafana
In the dashboard
SN 22231100Import total–
SN 22231101Import total–
SN 22231102Import total–
Modbus RTU request

The M-Center queries each Professional II on the RS-485 line: slave address, function code 03, register 6000. The meter replies with its meter reading.

Simplified illustration. Serial numbers, addresses and values are examples. In operation, the M-Center reads every 15 minutes by default.

How the gateway works

Meters, inverters and other devices with an RS-485 interface mostly speak Modbus RTU. The M-Center has two RS-485 ports for two Modbus RTU lines and reads up to 64 devices through them.

The M-Center then publishes the values to your MQTT broker, locally or in the cloud, with its own topic per device and register, optionally with TLS.

The values read are available via MQTT regardless of the storage setting. In addition, the M-Center stores the registers with «Save in database» enabled in its internal 16 GB memory.

How the devices get into the M-Center

  1. Connect the devices in a line to one of the two RS-485 lines of the M-Center and terminate the cable at both ends.
  2. Add the device in the web interface: choose the line, enter the serial number and the Modbus slave address.
  3. Set baud rate, data bits, parity and stop bit as on the device, plus byte and word order.
  4. Apply a Modbus driver or create registers: start address (from 1), function code 03 or 04, data type, unit, divisor and OBIS code.
  5. Activate MQTT: enter broker, port, user and password, prefix, TLS and QoS.

Newly created Modbus registers are not saved automatically. First check that the value is correct, then enable «Save in database». Modbus drivers can be exported as JSON and transferred to other M-Centers.

How the topics are structured

<prefix>/emu/mcenter/<MAC M-Center>/meterreading/<serial number>/byregister/<register number>
<prefix>/emu/mcenter/<MAC M-Center>/meterreading/<serial number>/byobis/<OBIS code>

The serial number in the topic is the number you enter when creating the Modbus device, so choose it uniquely. For topics by OBIS code, enter the OBIS code for the registers; active energy import, for example, is then under the same topic ending for every device.

Check the messages with an MQTT client such as MQTT Explorer before processing them further.

Order numbers

Article numberDescriptionShop
210.000.00EMU M-Center for 20 M-Bus devicesShop: EMU M-Center 210.000.00 →
210.200.00M-Center | Licence RS485 32 devices
210.200.01M-Center | Licence RS485 64 devices
210.300.03M-Center | Licence MQTT

Order online in the EMU Metering shop.

Licences can be activated later at any time, without changing hardware. M-Bus, RS485, Modbus TCP and all output interfaces run in parallel.

Frequently asked questions


How many RS485 devices does the M-Center read?

Up to 64 Modbus RTU devices on two lines. Licence 210.200.00 covers 32 devices, 210.200.01 covers 64 devices.

Do I need a cloud for MQTT?

No. The broker can run on the local network, for example on a server or in Home Assistant. The M-Center only needs a network connection to the broker.

Can I use M-Bus, RS485 and Modbus TCP at the same time?

Yes. All devices appear in the same device lists, and the M-Center provides their values simultaneously via all licensed interfaces, such as BACnet IP, MQTT, Modbus TCP or OPC UA.

How often does the M-Center read the devices?

Every 15 minutes by default. You can choose from 15 minutes to 28 days, also per device.