How the gateway works
Inverters, charging stations, meters and controllers on the network often deliver their values via Modbus TCP. With the licence «Modbus TCP 20 Devices», the M-Center reads up to 20 such devices as a Modbus TCP client.
The M-Center then provides each device in BACnet as its own device object and the measured values as analog input objects. The M-Center is B-ASC certified and supports BBMD.
The values read are available via BACnet IP regardless of the storage setting. In addition, the M-Center stores the registers with «Save in database» enabled in its internal 16 GB memory.
How the devices get into the M-Center
- Clarify the network: the M-Center and the devices must reach each other. Agree IP addresses and ports with IT.
- Add the device in the web interface: enter serial number, IP address, port and device address (slave ID). For the EMU Professional II any number from 0 to 255 works.
- Set byte and word order to match the device.
- Apply a Modbus driver or create registers: start address (from 1), function code 03 or 04, data type, unit, divisor and OBIS code.
- Activate BACnet IP: set the D-Net number, port and device instance of the M-Center and assign a BACnet instance number to each device.
Newly created Modbus registers are not saved automatically. First check that the value is correct, then enable «Save in database». Modbus drivers can be exported as JSON and transferred to other M-Centers.
BACnet IP settings
- D-Net number, port and device instance of the M-Center
- Instance number per device, in the device under «BACnet IP»
- BBMD enabled: access via the BBMD devices entered, using the two-hop broadcast method
- Continuous reading: the M-Center reads the devices continuously so that the values in BACnet are as current as possible
With «Continuous reading», only the values at the time of the reading interval are stored. BACnet and the other interfaces receive continuously updated values in between.
Order numbers
| Article number | Description | Shop |
|---|---|---|
| 210.000.00 | EMU M-Center for 20 M-Bus devices | Shop: EMU M-Center 210.000.00 → |
| 210.200.03 | M-Center | Licence Modbus TCP 20 devices | |
| 210.300.00 | M-Center | Licence BACnet IP |
Order online in the EMU Metering shop.
Licences can be activated later at any time, without changing hardware. M-Bus, RS485, Modbus TCP and all output interfaces run in parallel.